Hostname: page-component-cd9895bd7-gbm5v Total loading time: 0 Render date: 2024-12-26T06:57:13.309Z Has data issue: false hasContentIssue false

Reduction of airborne and surface-borne bacteria in a medical center burn intensive care unit using active, upper-room, germicidal ultraviolet (GUV) disinfection

Published online by Cambridge University Press:  25 October 2023

Linda D. Lee*
Affiliation:
UV Angel, Grand Haven, Michigan
Louise Lie
Affiliation:
Loyola University Medical Center, Maywood, Illinois
Michael Bauer
Affiliation:
Loyola University Medical Center, Maywood, Illinois
Berenice Bolanos
Affiliation:
Loyola University Medical Center, Maywood, Illinois
Russell N. Olmsted
Affiliation:
Trinity Health, Livonia, Michigan
Jay K. Varma
Affiliation:
Weill Cornell Medical College, New York, New York
Jorge P. Parada
Affiliation:
Loyola University Medical Center, Maywood, Illinois Loyola University Chicago, Chicago, Illinois
*
Author for correspondence: Linda D. Lee, DrPH, MBA, UV Angel, 233 Washington Ave, Suite L1, Grand Haven, MI 49417. E-mail: llee@uvangel.com
Rights & Permissions [Opens in a new window]

Abstract

Objective:

To determine the effectiveness of active, upper-room, germicidal ultraviolet (GUV) devices in reducing bacterial contamination in patient rooms in air and on surfaces as a supplement to the central heating, ventilation, and air conditioning (HVAC) air handling unit (AHU) with MERV 14 filters and UV-C disinfection.

Methods:

This study was conducted in an academic medical center, burn intensive care unit (BICU), for 4 months in 2022. Room occupancy was monitored and recorded. In total, 402 preinstallation and postinstallation bacterial air and non–high-touch surface samples were obtained from 10 BICU patient rooms. Airborne particle counts were measured in the rooms, and bacterial air samples were obtained from the patient-room supply air vents and outdoor air, before and after the intervention. After preintervention samples were obtained, an active, upper-room, GUV air disinfection system was deployed in each of the patient rooms in the BICU.

Results:

The average levels of airborne bacteria of 395 CFU/m3 before GUV device installation and 37 CFU/m3 after installation indicated an 89% overall decrease (P < .0001). Levels of surface-borne bacteria were associated with a 69% decrease (P < .0001) after GUV device installation. Outdoor levels of airborne bacteria averaged 341 CFU/m3 in March before installation and 676 CFU/m3 in June after installation, but this increase was not significant (P = .517).

Conclusions:

Significant reductions in air and surface contamination occurred in all rooms and areas and were not associated with variations in outdoor air concentrations of bacteria. The significant decrease of surface bacteria is an unexpected benefit associated with in-room GUV air disinfection, which can potentially reduce overall bioburden.

Type
Original Article
Creative Commons
Creative Common License - CCCreative Common License - BY
This is an Open Access article, distributed under the terms of the Creative Commons Attribution licence (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted re-use, distribution and reproduction, provided the original article is properly cited.
Copyright
© The Author(s), 2023. Published by Cambridge University Press on behalf of The Society for Healthcare Epidemiology of America

The recent epidemic waves have exposed the vulnerability of our social infrastructure to disease dissemination, and additional engineering controls focused on airborne pathogens are needed. The COVID-19 pandemic, a resurgence of endemic respiratory viruses [eg, respiratory syncytial virus (RSV), influenza, and rhinoviruses], and the increase in healthcare-associated infections (HAI) have highlighted the need for air disinfection in indoor environments. HAIs and multidrug-resistant organisms (MDROs) Reference Chezganova, Efimova and Sakharova1 are also persistent indoor air problems that may be treated with germicidal ultraviolet (GUV) disinfection technologies, including upper-level, in-room UV and surface treatment systems. 25 GUV disinfection technology has a long history of successful applications in both air and surface disinfection in hospitals, schools, government facilities, and commercial office buildings. Reference Kowalski6 When properly designed, GUV air-treatment systems can provide benefits in reduced incidence of respiratory disease, reduced asthma symptoms, and energy savings without harm to occupants. Reference Ryan7Reference Hart13,Reference Schneiter, Hollaender and Caminita34

The US Environmental Protection Agency issued the Clean Air in Buildings Challenge in 2022 to encourage and support improving indoor air quality. 14 Recommendations have included enhancing ventilation, air filtration, and adding GUV air-cleaning devices. The Centers for Disease Control (CDC) states that GUV can be a supplemental treatment to inactivate SARS-CoV-2 when options for increasing room ventilation and air filtration are limited. 4 In addition, American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Standard 170-2021 provides guidelines for filtration efficiencies, air changes per hour, and fresh air requirements for healthcare environments. 15

Air disinfection may reduce the incidence of respiratory infection in office workers, school-aged children and others, and it may benefit burn trauma patients, for whom infections are common. Reference Ryan7Reference Henle, Sommer and Stokes12 Burn-related infections hamper wound healing, lengthenroom hospital stays, increase healthcare costs, and mortality rates can reach 33%–80%. Reference Hart1315 Burn patients are at increased risk for HAIs as a result of the breakdown of the skin barrier and the profound systemic immunocompromising effects of the burn. Reference Escandón-Vargas, Tangua and Medina16 In addition, the lengthy admissions of these patients make time-consuming terminal cleaning a challenge during the patient’s admission.

A previous study demonstrated that the installation of multiple fixed-in-room upper GUV air cleaners significantly reduced both airborne and surface-borne bacterial contamination in high-occupancy areas of public restaurants, offices, and media-production trailers. Reference Lee, Delclos, Berkheiser, Barakat and Jensen17 These GUV systems did not affect the supply air to the rooms, the flow rate of which remained unchanged throughout testing. In the current study, fixed-in-room GUV air cleaners were installed in multiple patient rooms in a hospital burn unit to test whether similar results could be obtained in a healthcare environment. Recently, our study site has seen a significant increase in Candida auris cases. The GUV system was installed as one of the mitigation measures to address this outbreak.

Methods

This study was carried out at the Loyola University Medical Center Burn Intensive Care Unit (BICU) in Maywood, Illinois, over 4 months in 2022. The BICU is a 10-bed unit providing care to neonate, pediatric, and adult burn patients. The air disinfection system (UV Angel Clean Air, UV Partners, Grand Haven, MI) consists of a UV germicidal lamp (254 nm, 27 W UV output) enclosed within a high-intensity sealed chamber through which fans draw air through a MERV 7 filter. The total power draw for the unit is 115W. A constant airflow of 0.0236 m3/sec (50 cfm) airflow is exposed to the UV germicidal lamp inside the irradiation chamber during each pass, with an exposure time of ∼0.7 seconds. These units are integrated into a 2-foot (50-cm) × 4-foot (122-cm) light fixture installed in the ceiling. The unit weighs ∼22 pounds (∼10 kg).

The GUV in-room devices used in this study are not connected to the central heating, ventilation, and air conditioning (HVAC) air handling unit (AHU) and operate independently of all AHU controls. The advantage of the localized placement of GUV air-cleaning units is that contaminants remain in the room or area where they are released and are disinfected before migrating to other building areas. The GUV units utilized do not expose room occupants to UV due to the sealed chamber. Being fixed above the ceiling, the GUV air cleaners present no obstacles and are effectively invisible to occupants. They do not take up valuable floor space, and they operate automatically, requiring only annual lamp and filter replacement.

Air and surface samples were collected in various rooms throughout the day to establish a preinstallation baseline of contamination. Outdoor bacterial counts were measured as a reference. In each room, ∼11 preinstallation samples were collected. In addition, 10 postinstallation samples were collected from each room after installation of the GUV devices. All samples were obtained during normal hours of occupation without regard to the daily cleaning schedule. The ICU room size ranged from 175 square feet (16 m2) to 220 square feet (20.5 m2). All rooms had 9-foot (2.75 m) ceilings. Table 1 shows the room airflows and mean occupancy. Occupancy in the rooms was monitored before and after installation. Each occupancy number included the single patient and any attending healthcare providers when the sample was collected. Outdoor air samples were collected each morning and each afternoon for a total of 8 outdoor air samples: 4 before installation and 4 after installation of the UV Angel air units.

Table 1. Room Volume, Airflow, and Occupancy

Note. cfm, cubic feet per minute.

All mitigated patient rooms had 2 GUV units. On average, the ratio of air treatment units to cubic feet was 1:990 cubic feet. After installation of the GUV systems, matched air and surface samples were retaken in the same locations. The central HVAC (AHU) system was reported to have a UV-C coil cleaning system in the AHU and MERV 14 air filters for the supply air. This system was reported by hospital facilities to be compliant with the requirements of ASHRAE 170 for this type of hospital unit. 15 The air supplied by the central AHU was sampled to determine the CFU contribution delivered to the rooms. The hospital reported no change in cleaning procedures or AHUs before or during the study.

Air sampling

Bacterial air samples were collected once per hour per occupied sample location over a 2-day, 16-hour period randomly within the patient rooms. In total, 100 air samples were obtained before installation, and 101 air samples were collected after the GUV device installation. The supply air was collected in the room following the same protocol using capture ventilation hoods. All patient rooms were sampled (room numbers 31–35 and 41–45). On average, before installation, most rooms were sampled 11 times over 16 hours. Only 1 preinstallation sample was collected from patient room 33 due to the medical condition of the patient in the room; the staff advised the technicians not to access that room. In the postinstallation sampling, all patient rooms were sampled 10 times over 16 hours. Each room was also sampled for the bacterial CFU counts from the supplied air in each sampling round. Preinstallation sampling occurred in March, followed by the GUV installation according to hospital infection control risk assessment (ICRA) protocols. Postinstallation sampling occurred in June. Environmental Molecular Services Laboratory (Houston, TX), processed all the sample plates.

An SAS 180 Air Sampler (Bioscience International, Rockville, MD) was used to sample the air. The D50 particle cutoff size for the SAS sampler was 1.51 µm. The aspirating head was cleaned with isopropyl alcohol and was allowed to dry before use. Sample plates (90 mm diameter) containing TSA with blood agar were inserted into the sampler, operated by a timer for ∼5.5 minutes, drawing 1,000 L of air. Samplers were positioned 1–1.5 m above the floor to collect samples in the breathing zone. The SAS sampler was in current calibration, and air sampling data (CFU counts) were corrected according to the SAS sampler instruction manual. 18 Air bacteria concentrations were measured in colony-forming units (CFU) per cubic meter. The sampled CFU per 1,000 L (CFU/m3) were corrected according to the following equation:

(1) $$x = {{1,000Pr} \over V}$$

where x is the CFU/m3 of air; Pr is the probable count obtained by positive hole correction; and V is the volume of air sampled (1,000 L). The value of Pr was obtained from a correction table in the instruction manual. 18 Because the maximum value of Pr =1,307 at a plate count of 219, any CFU values >219 were assumed to have a maximum value of Pr = 1,308.

Air sampling included collecting samples and metrics from the supply air vents, including viable bacteria counts, particle counts, relative humidity, temperature, and airflow in cubic feet per minute (cfm). Capture ventilation hoods were used to isolate the “clean” air supply to the room from the central AHU to collect bacteria levels. The preinstallation CFUs in the supply air were measured when no ceiling GUV devices were operating in the room, and levels were measured again when the ceiling GUV devices were operating in the patient rooms.

Surface sampling

Surface samples were obtained using replicate organism detection and counting (RODAC) plates before and after installation in the same rooms and areas where air samples were collected. Some 99 preinstallation surface samples and 102 postinstallation surface samples were obtained from the 10 rooms. Surface samples were obtained from non–high-touch surfaces. The RODAC plates included tryptic soy agar supplemented with lecithin and tween to neutralize residues from chemical disinfectants. Firm pressure was applied to each plate for 30 seconds. Surface bacteria concentrations were measured in CFU per 25-cm 2 plate, and values were summarized in units of CFU per plate. All surfaces sampled were identified as horizontal non–high-touch surfaces, such as the tops of shelves, tabletops, the top of televisions, headwall lights, rear area of sinks, etc. Postinstallation surface samples were matched at locations immediately adjacent to the locations where the preinstallation samples were collected.

Particle counting

A model PCO-1 air sampler was used for particle counting. 19 Particle counts were measured at 2.5 µm and 0.3 µm in all rooms and the outside air. In total, 197 particle-count samples were collected in the rooms before GUV device installation, and 4 control samples of the outside air were collected. In total, 212 particle-count samples were collected in the rooms after installation, and 4 control samples of the outside air were also collected.

Statistical methods

Data were analyzed using statistical software NCSS version 11 software. 20 Means, and standard deviations of data were analyzed using analysis of variance (ANOVA). Statistical significance was set at α = .05 to determine the P values for air samples, surface samples, and particle counts. Due to the nonnormality of the sample data and high variance, an Aspin-Welch unequal variance 2-sample t test was used for correlations.

Results

Overall airborne bacteria concentrations had a mean preinstallation value of 395 CFU/m3 (n = 100; standard error of the mean [SEM] = 12 CFU/m3) and a postinstallation value of 37 CFU/m3 (n = 100; SEM = 12 CFU/m3; P < .0001), representing a decrease of 89%. Room surface bacteria concentrations had a mean preinstallation value of 21 CFU/m3 (n = 100; SEM = 1 CFU/m3) and a mean postinstallation value of 7 CFU/m3 (n = 101; SEM = .6 CFU/m3; P < .0001), representing a decrease of 69%. Figure 1 illustrates these results along with the SEM. The outdoor air concentrations increased from an average of 341 CFU/m3 (n = 4; SEM = 323 CFU/m3) before installation to 676 CFU/m3 (n = 4; SEM = 365 CFU/m3) after installation, but this increase was not significant (P = .517). Table 2 summarizes the concentration reductions for the individual rooms and associated P values. The total airborne viable bacterial CFU before and after the installation of GUV air-cleaning devices (395 vs 37 CFU/m3, respectively) in the BICU represented an average reduction of 89% and a range of 76%–94% in the rooms.

Figure 1. Comparison of before versus after overall room average colony-forming units (CFU) for germicidal ultraviolet light (GUV) in air (CFU/m3) and on surfaces (CFU/plate).

Table 2. Average Mitigated CFUs for Airborne and Surface Samples With Aspin-Welch Unequal Variance T-Test P Values Before and After Installation of a UV-C Air Cleaning Unit

Note. CFU, colony-forming units.

Figures 2 and 3 show the preinstallation versus postinstallation airborne and surface concentrations for the individual rooms. No significant difference was seen in the bacteria counts of the air supplied to the room (Table 3). Room supply and exhaust airflows were monitored before and after the test and did not vary significantly. Supply airflows ranged from 10.6 to 14.4 m3/min and from 12.9 to 18.8 air changes per hour (ACH). Temperature and relative humidity were monitored throughout the test and remained at 59–82°F (15–28°C) and 19%–69%, respectively.

Figure 2. Comparison of total airborne colony-forming units (CFU) in each room with and without germicidal ultraviolet light (GUV) device. Error bars show the standard error of the mean (SEM) values.

Figure 3. Comparison of total surface-borne colony-forming units (CFU) in each room with and without a germicidal ultraviolet light (GUV) device. Error bars show the SEM values.

Table 3. Average Supply Hood CFUs for Airborne Samples With Aspin-Welch Unequal Variance T Test P Values Before and After Installation of a UV-C Air Cleaning Unit

Note. CFU, colony-forming units.

An average of 2.73 occupants per room per day before installation and 1.64 occupants per room per day after installation was not a statistically significant difference (P = .571). The CFU counts in the air supplied to the rooms, 3.1 CFU/m3 before installation and 3.4 CFU/m3 after installation, were very low compared to the CFU counts in the air in the room, 395 CFU/m3 before installation and 37 CFU/m3 after installation. These approximate proportions of supplied air remained consistent before and after GUV installation.

Particle counts showed large reductions between the pre- and postinstallation measurements (Table 4). For the smaller 0.3-µm particle sizes, the outdoor air percentage difference between preinstallation and postinstallation testing was 69% but was not statistically significant (P = .561). In contrast, the difference between the rooms was 56% with the GUV device (P = .048). For the larger 2.5-µm particles, the outdoor air change was 57% (P = .03). Particle counts with the GUV device in the rooms were 69% lower (P < .0001) overall. Surface sampling data before and after installation indicated an average 69% reduction in total settled surface bacteria CFU: 21 versus 7 (P < .0001).

Table 4. Particle Counts in Rooms and Supply Hoods Before and After Installation of a UV-C Air Cleaning Unit

Discussion

These results corroborate earlier studies on the same or similar GUV air disinfection devices in which airborne bacteria levels were significantly reduced. Reference Lee, Delclos, Berkheiser, Barakat and Jensen17,Reference Ethington, Newsome, Waugh and Lee21Reference Hakim, Gilliam, Tang, Xu and Lee24 Previous studies have demonstrated that GUV can be effective at reducing airborne concentrations for a wide variety of pathogens, including M. tuberculosis, Staphylococcus aureus, S. albus, E. coli, Streptococcus pneumoniae, Serratia marcescens, Pseudomonas aeruginosa, P. fluorescens, Proteus vulgaris, Moraxella catarrhalis, influenza A, SARS-CoV-2 coronavirus, and various other pathogens that cause upper-respiratory infections. Reference Menzies, Comtois, Pasztor, Nunes and Hanley8Reference Schneider, Schwartenberg and Amiel10,Reference Henle, Sommer and Stokes12,Reference Hart13,Reference Kane, Finley and Brown23Reference Riley and O’Grady33

The result that air disinfection is significantly associated with the reduction of surface contamination is an important finding and corroborates previous studies. This important finding supports the concept that treating the air directly impacts surface contamination, where settled bacteria can be re-entrained by local air currents. Airborne bacteria settle out of the air at a rate that depends on their aerodynamic size. Reference Kowalski6 This result corroborates a previously published study that reported a 55% reduction in surface contamination with the same GUV air-cleaning system applied in commercial environments. Reference Lee, Delclos, Berkheiser, Barakat and Jensen17 GUV air disinfection may mitigate surface-borne disease transmission by reducing fomites, and some supportive evidence for this comes from testing of GUV devices in animal facilities wherein the level of transmission of nonrespiratory pathogens was reduced by UV air cleaning. Reference Bernstein, Bobbitt and Levin35 This finding was also supported by a study conducted in a hospital ICU by Ethington et al, Reference Ethington, Newsome, Waugh and Lee21 where a similar technology was associated with an overall 60% decrease in HAIs.

Although this air disinfection system does not exceed the surface reductions achieved by a dedicated terminal cleaning process, it removes a significant amount of settled surface-borne bacteria as a benefit of air disinfection. Continuous air treatment compliments the episodic patient room cleaning (routine and terminal). These are important considerations in a multilayered approach to infection prevention and control. Depending on the application, GUV technology may not be prohibitively expensive, but the question of cost may represent a study limitation; thus, cost-effectiveness should be considered in future research.

These results suggest that active, upper-room, GUV air disinfection can reduce levels of air and surface contamination and can diminish the total bioburden of the indoor environment. GUV can significantly reduce airborne concentrations in buildings in the same way that ventilation dilution reduces airborne concentrations—the addition of clean air to the building displaces contaminated air, and the indoor contaminant concentration decreases rapidly over time.

In high-density, high-contamination scenarios, or with high-risk patients, filtration and ventilation may not be enough. The reductions observed in this study of upper in-room GUV occurred in the setting of a pre-existing MERV 14 and UVC in the AHU and up to 18.8 ACH. Considering the AHU delivered, on average, 3 CFU/m3 of bacteria to the room, the high levels of CFUs in the patient room before the mitigation were due to people and patient care activities in the room. Installing the mitigation device at the point of care significantly reduced the viable bacteria levels in the patient room. The AHU alone did not reduce the viable bacteria load in this critical care area. This supplemental engineering control may improve the safety of highly susceptible patients following burn injury.

Our findings highlight the benefit of continuous versus episodic cleaning of the room, and these processes work together for a cleaner space. Patients in the BICU have lengthy admissions (the median BICU stay is 22 days). Continuous operation of the GUV system reduces the bioburden in this high-risk environment.

GUV active air-cleaning technology had a size-dependent effect on the particles in the room. Smaller particles of the 2.5-µm size range experienced significantly greater reductions in indoor air (69%) versus outdoor air (57%). The MERV 7 filter in the air disinfection unit may have also contributed to this decrease. More study is needed regarding minimizing particle concentrations by GUV air disinfection.

This study had several limitations. For example, the study duration was too short to measure any reductions in disease incidence, an area for much-needed future research. High-touch surfaces were not investigated. Our follow-up research will investigate the transmission of infections to patients and patient infection rates, and the cost-effectiveness of the application was not evaluated.

The data analyzed in this study suggest that in-room, active, supplementary, upper-room UV-C disinfection may decrease the concentration of bacteria in the air and on settled surfaces. The advantages of engineering control include (1) continuous operation, (2) not user dependent, and (3) safer environment of care, especially for those highly susceptible to cross infection and employees. Traditional air change rates may have limited effectiveness in critical care applications, such as BICU; thus, it may be time to consider supplemental environmental air cleaning technologies such as active GUV air disinfection.

Acknowledgments

Financial support

This study was supported by and funded by UV Angel in cooperation with Loyola University Medical Center. UV Angel provided the study design (following previous studies), industrial hygiene technician support of sample collection, and data analysis. Oversight of sample collection was provided by Loyola facilities management and infection prevention. EMSL laboratory provided the sample analysis. Manuscript preparation was a collaborative effort between Loyola Infection Prevention and UV Angel, with Dr Lee taking the lead role.

Competing interest

L.D.L. has a consulting agreement with UV Angel and was compensated for the study. R.N.O. reports grant support for affiliated Health Systems by MI Medicine (Ann Arbor), consulting fee paid by STI Technologies and Northshore University Health System. All other authors report no conflicts of interest relevant to this article.

References

Chezganova, E, Efimova, O, Sakharova, V, et al. Ventilation-associated particulate matter is a potential reservoir of multidrug-resistant organisms in health facilities. Life (Basel) 2021;11:639.Google ScholarPubMed
American Society of Heating, Refrigerating and Air-Conditioning Engineers. ASHRAE position document on infectious aerosols. Atlanta: ASHRAE; 2020.Google Scholar
American Society of Heating, Refrigerating and Air-Conditioning Engineers. ASHRAE epidemic task force core recommendations for reducing infectious aerosol exposure. ASHRAE. Atlanta: ASHRAE; 2021.Google Scholar
Ventilation in buildings. Centers for Disease Control and Prevention website. https://www.cdc.gov/coronavirus/2019-ncov/community/ventilation.html. Published 2021. Accessed October 2, 2023.Google Scholar
Environmental control for tuberculosis: basic upper-room ultraviolet germicidal irradiation guidelines for healthcare settings. Centers for Disease Control and Prevention website. https://www.cdc.gov/niosh/docs/2009-105/pdfs/2009-105.pdf. Published 2009. Accessed October 2, 2023.Google Scholar
Kowalski, WJ. Ultraviolet Germicidal Irradiation Handbook: UVGI for Air and Surface Disinfection. New York: Springer; 2009.CrossRefGoogle Scholar
Ryan, CW. Decreased respiratory-related absenteeism among preschool students after installation of upper-room germicidal ultraviolet light: analysis of newly discovered historical data. Int J Envir Res Public Health 2023;20(2536).CrossRefGoogle ScholarPubMed
Menzies, D, Comtois, P, Pasztor, J, Nunes, F, Hanley, JA. Aeroallergens and work-related respiratory symptoms among office workers. J Allergy Clin Immunol 1998;101:3844.CrossRefGoogle ScholarPubMed
Dionne, J-C. Assessment of an ultraviolet air sterilizer on the incidence of childhood respiratory tract infections and day care centre indoor air quality. Indoor Environ 1993;2:307311.Google Scholar
Schneider, M, Schwartenberg, J, Amiel, JL, et al. Pathogen-free isolation unit—three years’ experience. Brit Med J 1969;29:836839.CrossRefGoogle Scholar
Wheeler, SM, Ingraham, HS, Hollaender, A, Lill, ND, Gershon-Cohen, J, Brown, EW. Ultraviolet light control of airborne infections in a naval training center. Am J Pub Health 1945;35:457468.CrossRefGoogle Scholar
Henle, W, Sommer, HE, Stokes, J. Studies on airborne infection in a hospital ward: II. Effects of ultraviolet irradiation and propylene glycol vaporization upon the prevention of experimental airborne infection of mice by droplet nuclei. J Pediatr 1942;21:577590.CrossRefGoogle Scholar
Hart, J. Sterilization of air in operating room by special bactericidal radiant energy. J Thoracic Surg 1936;6:4581.CrossRefGoogle Scholar
EPA Clean Air in Buildings Challenge. Ft. Meade, MD: US EPA; 2022.Google Scholar
American Society of Heating, Refrigerating and Air-Conditioning Engineers. ANSI/ASHRAE/ASHE standard 170-2021, ventilation of health care facilities. Atlanta: ASHRAE; 2021.Google Scholar
Escandón-Vargas, K, Tangua, AR, Medina, P, et al. Healthcare-associated infections in burn patients: timeline and risk factors. Burns 2020;46:17751786.CrossRefGoogle ScholarPubMed
Lee, LD, Delclos, G, Berkheiser, ML, Barakat, MT, Jensen, PA. Evaluation of multiple fixed in-room air cleaners with ultraviolet germicidal irradiation, in high-occupancy areas of selected commercial indoor environments. J Occup Environ Hyg 2022;19:6777.CrossRefGoogle ScholarPubMed
PBI Air Sampling Instruction Manual: SAS Super 100, SAS Super 180, Duo SAS Super 360. LaPorte, TX: PBI International; 2001.Google Scholar
PCE Air Sampler PCE-PC01 Instruction Manual. Jupiter, FL: PCE Americas; 2019.Google Scholar
NCSS. NCSS Statistical Analysis and Graphics Software. East Kaysville, UT: NCSS; 2016.Google Scholar
Ethington, T, Newsome, S, Waugh, J, Lee, LD. Cleaning the air with ultraviolet germicidal irradiation lessened contact infections in a long-term acute-care hospital. Am J Infect Control 2018;46:482486.CrossRefGoogle Scholar
Guimera, D, Trzil, J, Joyner, J, Hysmith, ND. Effectiveness of a shielded ultraviolet C air disinfection system in an inpatient pharmacy of a tertiary-care children’s hospital. Am J Infect Control 2018;46:223225.CrossRefGoogle Scholar
Kane, D, Finley, C, Brown, D. UV-C light and infection rate in a long-term care ventilator unit. Can J Infect Control 2018;33:4448.Google Scholar
Hakim, H, Gilliam, C, Tang, L, Xu, J, Lee, LD. Effect of a shielded continuous ultraviolet-C air disinfection device on reduction of air and surface microbial contamination in a pediatric oncology outpatient care unit. Am J Infect Control 2019;47:12481254.CrossRefGoogle Scholar
Allegra, L, Blasi, F, Tarsia, P, Arosio, C, Fagetti, L, Gazzano, M. A novel device for the prevention of airborne infections. J Clinical Microb 1997;35:19181919.CrossRefGoogle ScholarPubMed
Andersen, BM, Banrud, H, Boe, E, Bjordal, O, Drangsholt, F. Comparison of UV C light and chemicals for disinfection of surfaces in hospital isolation units. Infect Control Hosp Epidemiol 2006;27:729734.CrossRefGoogle ScholarPubMed
Wells, W. Airborne Contagion. New York: New York Academy of Sciences; 1955.Google Scholar
Rosenstern, I. Control of airborne infections in a nursery for young infants. Am J Dis Child 1948;75:193202.Google Scholar
Rentschler, H, Nagy, R. Bactericidal action of ultraviolet radiation on airborne microorganisms. J Bacteriol 1942;44:8594.CrossRefGoogle Scholar
Barenberg, LH, Greene, D, Greenspan, L. Effect of the irradiation of the air in a ward on the incidence of infections of the respiratory tract. JAMA Pediatr 1940;59:12191226.Google Scholar
Sharp, G. The effects of ultraviolet light on bacteria suspended in air. J Bact 1940;38:535547.CrossRefGoogle Scholar
Robertson, EC, Doyle, ME, Tisdall, FF, Koller, LR, Ward, FS. Air contamination and air sterilization. Am J Dis Child 1939;58:10231037.Google Scholar
Riley, RL, O’Grady, F. Airborne Infection. New York: Macmillan; 1961.Google Scholar
Schneiter, R, Hollaender, A, Caminita, BH, et al. Effectiveness of ultraviolet irradiation of upper air for the control of bacterial air contamination in sleeping quarters. Am J Hyg 1944;40:136.Google Scholar
Bernstein, J, Bobbitt, R, Levin, L, et al. Health effects of ultraviolet irradiation in asthmatic children’s homes. J Asthma 2006;43:255262.CrossRefGoogle ScholarPubMed
Jaynes, RA, Thompson, MC, Kennedy, MA. Effect of ultraviolet germicidal irradiation of the air on the incidence of upper respiratory tract infections in kittens in a nursery. J Am Vet Med Assoc 2020;257:929932.CrossRefGoogle Scholar
Figure 0

Table 1. Room Volume, Airflow, and Occupancy

Figure 1

Figure 1. Comparison of before versus after overall room average colony-forming units (CFU) for germicidal ultraviolet light (GUV) in air (CFU/m3) and on surfaces (CFU/plate).

Figure 2

Table 2. Average Mitigated CFUs for Airborne and Surface Samples With Aspin-Welch Unequal Variance T-Test P Values Before and After Installation of a UV-C Air Cleaning Unit

Figure 3

Figure 2. Comparison of total airborne colony-forming units (CFU) in each room with and without germicidal ultraviolet light (GUV) device. Error bars show the standard error of the mean (SEM) values.

Figure 4

Figure 3. Comparison of total surface-borne colony-forming units (CFU) in each room with and without a germicidal ultraviolet light (GUV) device. Error bars show the SEM values.

Figure 5

Table 3. Average Supply Hood CFUs for Airborne Samples With Aspin-Welch Unequal Variance T Test P Values Before and After Installation of a UV-C Air Cleaning Unit

Figure 6

Table 4. Particle Counts in Rooms and Supply Hoods Before and After Installation of a UV-C Air Cleaning Unit